کنتاکتور اشنایدر الکتریک 12 آمپر 220 ولت AC
کنتاکتور اشنایدر الکتریک 12 آمپر 220 ولت AC
TeSys D contactor – 3P(3 NO) – AC-3 – <= 440 V 12 A – 220 V AC coil
| range | 
 TeSys 
 | 
|
|---|---|---|
| product name | 
 TeSys D 
 | 
|
| product or component type | 
 Contactor 
 | 
|
| device short name | 
 LC1D 
 | 
|
| contactor application | 
 Resistive load 
Motor control  | 
|
| utilisation category | 
 AC-4 
AC-1 AC-3  | 
|
| poles description | 
 3P 
 | 
|
power pole contact composition | 
 3 NO 
 | 
|
| [Ue] rated operational voltage | 
 Power circuit: <= 690 V AC 25…400 Hz 
Power circuit: <= 300 V DC  | 
|
| [Ie] rated operational current | 
 25 A (at <60 °C) at <= 440 V AC AC-1 for power circuit 
12 A (at <60 °C) at <= 440 V AC AC-3 for power circuit  | 
|
| motor power kW | 
 3 kW at 220…230 V AC 50/60 Hz (AC-3) 
5.5 kW at 380…400 V AC 50/60 Hz (AC-3) 5.5 kW at 415…440 V AC 50/60 Hz (AC-3) 7.5 kW at 500 V AC 50/60 Hz (AC-3) 7.5 kW at 660…690 V AC 50/60 Hz (AC-3) 3.7 kW at 400 V AC 50/60 Hz (AC-4)  | 
|
| motor power HP (UL / CSA) | 
 0.5 hp at 115 V AC 50/60 Hz for 1 phase motors 
2 hp at 230/240 V AC 50/60 Hz for 1 phase motors 3 hp at 200/208 V AC 50/60 Hz for 3 phases motors 3 hp at 230/240 V AC 50/60 Hz for 3 phases motors 7.5 hp at 460/480 V AC 50/60 Hz for 3 phases motors 10 hp at 575/600 V AC 50/60 Hz for 3 phases motors  | 
|
| control circuit type | 
 AC at 50/60 Hz 
 | 
|
| [Uc] control circuit voltage | 
 220 V AC 50/60 Hz 
 | 
|
| auxiliary contact composition | 
 1 NO + 1 NC 
 | 
|
| [Uimp] rated impulse withstand voltage | 
 6 kV conforming to IEC 60947 
 | 
|
| overvoltage category | 
 III 
 | 
|
| [Ith] conventional free air thermal current | 
 25 A (at 60 °C) for power circuit 
10 A (at 60 °C) for signalling circuit  | 
|
| Irms rated making capacity | 
 250 A at 440 V for power circuit conforming to IEC 60947 
140 A AC for signalling circuit conforming to IEC 60947-5-1 250 A DC for signalling circuit conforming to IEC 60947-5-1  | 
|
| rated breaking capacity | 
 250 A at 440 V for power circuit conforming to IEC 60947 
 | 
|
[Icw] rated short-time withstand current | 
 105 A 40 °C – 10 s for power circuit 
210 A 40 °C – 1 s for power circuit 30 A 40 °C – 10 min for power circuit 61 A 40 °C – 1 min for power circuit 100 A – 1 s for signalling circuit 120 A – 500 ms for signalling circuit 140 A – 100 ms for signalling circuit  | 
|
| associated fuse rating | 
 10 A gG for signalling circuit conforming to IEC 60947-5-1 
40 A gG at <= 690 V coordination type 1 for power circuit 25 A gG at <= 690 V coordination type 2 for power circuit  | 
|
| average impedance | 
 2.5 mOhm – Ith 25 A 50 Hz for power circuit 
 | 
|
| [Ui] rated insulation voltage | 
 Power circuit: 690 V conforming to IEC 60947-4-1 
Power circuit: 600 V CSA certified Power circuit: 600 V UL certified Signalling circuit: 690 V conforming to IEC 60947-1 Signalling circuit: 600 V CSA certified Signalling circuit: 600 V UL certified  | 
|
| electrical durability | 
 2 Mcycles 12 A AC-3 at Ue <= 440 V 
0.8 Mcycles 25 A AC-1 at Ue <= 440 V  | 
|
| power dissipation per pole | 
 0.36 W AC-3 
1.56 W AC-1  | 
|
| Front cover | 
 With 
 | 
|
| mounting support | 
 Rail 
Plate  | 
	
					
					
					
					
					
					
					
					
					
					
				
				